KYN28A high voltage switchgearIt is a kind of high-voltage switchgear that is more common in China, the full name is indoor metal armored removable switchgear.

KYN28A high voltage switchgear manufacturer Derun Electric 400-128-7988

KYN28A high voltage switchgearIt is a kind of high-voltage switchgear that is more common in China, the full name is indoor metal armored removable switchgear.

Its rated voltage is 3.6kV~12kV, and its feature is that the equipped vacuum circuit breaker is mid-type, that is, the circuit breaker is located in the middle of the front cabinet of the switchgear, so the lower space can be saved for the expansion of other schemes or as a cable room.

KYN28 high-voltage switchgear refers to electrical products with a voltage level of 12kV for power system power generation, transmission, distribution, power conversion and consumption, including high-voltage circuit breakers, grounding switches, transformers, etc.

The high-voltage switch manufacturing industry is an important part of the power transmission and transformation equipment manufacturing industry and occupies a very important position in the entire power industry. Debugging is generally a routine process to test the safety and stability of equipment before replacing components or putting equipment back into use after failure. Below KYN28A high-voltage switchgear manufacturers, Anhui Derun Electric share KYN28A with youHigh voltage switchgearNine debugging steps now!

KYN28A High Voltage Switch Cabinet 400-128-7988 Anhui Derun Electric

1. Equipment introduction

High-voltage metal-enclosed switchgear is composed of two parts: cabinet and handcart.

The cabinet is divided by metal partitions into four separate compartments: busbar room, circuit breaker handcar room, cable room and relay instrument room. Hand cart according to the use is divided into circuit breaker hand car, metering hand car, isolation hand car, etc., the same parameter specifications of the hand car can be freely interchanged, the hand car in the cabinet has a test position and working position, each position has a device in place to ensure the reliability of interlocking, these are involved in the previous content of the electrical Baijia network.

The high-voltage switchgear has a safe and reliable interlocking device, which can meet the requirements of "five prevention":

1 Prevent misoperation of the circuit breaker;

2 Prevent pulling and closing the disconnector with load, that is, to prevent pushing and pulling trolleys with load;

3 Prevent live grounding wire, that is, prevent live grounding switch;

4 Prevent power transmission with grounding wire, that is, prevent power transmission when the grounding switch is in the grounded position;

5 Prevent misentry of live interval)

a) When the circuit breaker handcart is in the test or working position, the circuit breaker can only be combined and divided, and after the circuit breaker is closed, the handcart cannot move, which prevents the load from being pulled by mistake and inferring the circuit.

b) Only when the grounding off is in the open position, the circuit breaker handcart can be moved from the test position to the working position, and only when the circuit breaker handcart is in the test position, the grounding switch can be closed operation, which realizes the prevention of live misclosing of the grounding switch and the shutdown of the circuit breaker when the grounding switch is in the closed position.

c) When the grounding switch is in the opening position, the lower door and the rear door cannot be opened, which prevents the accidental entry of the live interval.

d) When the circuit breaker is in the working position, the secondary plug is locked and cannot be pulled out. In order to ensure safety and the reliability of each interlocking device from damage, it must be operated in accordance with the interlock anti-misoperation procedure.

Second, the main power cabinet power transmission operation seven steps

1) Close all doors and rear sealing plates and lock them.

2) Push on the transfer trolley and position it, push the circuit breaker trolley into the cabinet and position it in the test position, (when inferring the circuit breaker, you need to press the two push and pull handles of the circuit breaker to the middle, and at the same time push forward (push into the cabinet), after the circuit breaker reaches the test position, let go of the push and pull handle, and the handle should be automatically reset.) Manually plug in the aviation plug, close the handheld compartment door and lock it.

3) Observe whether the instruments and signal indications of the upper cabinet door are normal. (Normally, the comprehensive relay power supply light is on, the circuit breaker opening indicator and the energy storage indicator are on, if all the indicator lights are not on, open the cabinet door to confirm whether the bus power switch is closed, if the indicator lights are still not lit, the control loop needs to be repaired.) )

4) Insert the circuit breaker handcart crank into the crank socket and press down hard, turn the crank clockwise, about 20 turns, and remove the crank when the crank is obviously blocked and accompanied by a "click" sound, at this time the handcart is in the working position, the aviation plug is locked, the main circuit of the circuit breaker handcart is turned on, and the relevant signal is viewed. (Due to the mechanical interlocking between the main power supply and the backup power supply, when the main power circuit breaker is in the working position, the backup power circuit breaker must be in the experimental position)

5) Observe the live display and make sure that the external power supply has been sent to the cabinet. (The live monitor panel display light is lit to indicate that the external power supply has been sent to the lower contact of the circuit breaker in this cabinet.) If the live display light is not on, you need to send the external power to the cabinet first. )

6) Close the transfer switch to make the circuit breaker close and send power, at the same time the red closing indicator on the instrument door is on, the green opening indicator is off, check other related signals, everything is normal, and the power transmission is successful. (When operating the split and closing transfer switch, rotate the operating handle clockwise to the panel indicated closing position, and the operation handle should be automatically reset to the pre-closing position after releasing the hand.) )

7) If the circuit breaker is automatically opened after closing or automatically opened during operation, it is necessary to determine what kind of fault and eliminate it before re-transmitting power according to the above procedure. (When the line fault circuit breaker is opened, an audible and light alarm will be issued, that is, the red fault indicator light on the panel is on, and the signal screen fault sounds.) At this time, observe the comprehensive relay, if the protection trip light is on, the fault is line overcurrent, in the fault maintenance can press the signal screen return button to cancel the ringing, after the maintenance is completed, you need to press the comprehensive relay panel return button to manually reset the comprehensive relay. )

Third, the main power cabinet power failure operation five steps

1) Observe all cabinet related signals and confirm that all outlet cabinet circuit breakers are in the open position.

2) The sub-transfer switch makes the circuit breaker open and cut off, and at the same time the red closing indicator light on the instrument door is off, the green opening indicator is on, check other related signals, everything is normal, and the power failure is successful. (When operating the closing and sub-transfer switch, rotate the operating handle counterclockwise to the panel indication position, and the operating handle should be automatically reset to the pre-division position after releasing the hand.) )

3) Insert the circuit breaker handcart crank into the crank socket and press down hard, turn the crank counterclockwise, about 20 turns, remove the crank when the crank is obviously blocked and accompanied by a "click" sound, at this time the handcart is in the test position, the aviation plug lock is released, open the handcart room door, and manually disengage from the aviation plug. (The main circuit of the handcart is disconnected)

4) Observe the live display and confirm that it is not charged before continuing the operation. (The lower door of the incoming cabinet has an electromagnetic lock forced lock, which can only be unlocked when the incoming end is not charged, but it can also be urgently unlocked with a key when the incoming end is charged.) The opening of the incoming circuit breaker does not mean that the incoming cabinet is not electrified, such as the external power supply does not stop, at this time the cable room is with high voltage, and it is life-threatening to forcibly enter. )

5) Open the lower door, power inspection (necessary power inspection), discharge (necessary discharge), hang grounding wire (necessary grounding wire), maintenance personnel can enter maintenance, overhaul.

4. The operating procedures of the standby power cabinet are the same as those of the main power cabinet

Since the relevant content has been introduced earlier, that is, the seven steps of power transmission operation and the five steps of power failure operation, we will not expand on it.

5. Three steps of metering cabinet operation

1) The metering handcart is directly connected with dynamic and static contacts, does not have the ability to break and extinguish, and absolutely cannot be shaken in and out of the metering handcart with load.

2) The metering handcart and the incoming switchgear circuit breaker have electrical and mechanical interlocks, and can only be operated after the main power supply (backup power) circuit breaker is opened, and can only be operated in or out of the metering handcar, and cannot be forcibly operated to avoid damage to the interlocking device. When the metering handcart is forcibly shaken out with load, the main power supply (backup power) circuit breaker will automatically open to avoid personal injury or death.

3) The method of shaking in and out of the metering handcart is the same as the circuit breaker handcar.

Sixth, PT cabinet operation three steps

1) Rock into the PT handcart first.

2) Observe the live display, if the monitor light is on, then the 10kV high voltage has been sent to the cabinet, check whether the voltmeter is displayed normally.

3) The method of shaking in and out of the PT handcart is the same as the circuit breaker handcar.

7. Seven steps of power transmission operation in the outlet cabinet

1) Close all doors and rear sealing plates and lock them. (The lower door of the cabinet can only be closed when the grounding switch is in the closed position)

2) Insert the grounding switch operation handle into the hexagonal hole on the lower right side of the middle door, rotate counterclockwise to make the grounding switch in the opening position, take out the operation handle, and the interlocking plate at the operating hole automatically springs back, covering the operation hole, and the door under the cabinet is locked.

3) Push on the transfer trolley and position it, push the circuit breaker trolley into the cabinet and position it in the test position, (when inferring the circuit breaker, you need to press the two push and pull handles of the circuit breaker to the middle, and at the same time push forward (push into the cabinet), after the circuit breaker reaches the test position, let go of the push and pull handle, and the handle should be automatically reset. Manually plug in the aviation plug, close the handheld compartment door and lock it.

4) Observe whether the instruments and number indications of the upper cabinet door are normal. (Under normal circumstances, the comprehensive relay power supply light is on, the circuit breaker opening indicator and energy storage indicator are on, the grounding opening indicator is on, if all the indicator lights are not on, open the upper cabinet door to confirm whether the bus power switch is closed, if the indicator lights are still not lit, the control loop needs to be repaired.) )

5) Insert the circuit breaker handcart crank into the crank socket and press down hard, turn the crank clockwise, about 20 turns, and remove the crank when the crank is obviously blocked and accompanied by a "click" sound, at this time the handcart is in the working position, the aviation plug is locked, the main circuit of the circuit breaker handcart is turned on, and the relevant signal is viewed.

6) Operate the instrument door up and off, the transfer switch makes the circuit breaker close and send power, at the same time the red closing indicator on the instrument door is on, the green opening indicator is off, check the live display and other related signals, everything is normal, and the power transmission is successful. (When operating the closing and sub-transfer switches, rotate the operating handle clockwise to the panel indicating the closing position, and the operating handle should be automatically reset to the pre-closing position after releasing the hand.) If it cannot be closed normally, check whether the transformer door is closed.

7) If the circuit breaker is automatically opened after closing or automatically opened during operation, it is necessary to determine what kind of fault and eliminate it before re-transmitting power according to the above procedure. (When the line fault circuit breaker is opened, an audible and visual alarm will be issued, and the fault sound will sound.) At this time, observe the comprehensive relay, if the protection trip light is on, the fault is line overcurrent, after the maintenance is completed, you need to press the comprehensive relay panel return button to manually reset the comprehensive relay. )

8. Six steps for power failure operation in the outlet cabinet

1) Operate the instrument door up and off the transfer switch to make the circuit breaker open and power off, and at the same time the red closing indicator on the instrument door is off, the green opening indicator light is on, check other related signals, everything is normal, and the power failure is successful. (When operating the closing and sub-transfer switch, rotate the operating handle counterclockwise to the panel indication position, and the operating handle should be automatically reset to the pre-division position after releasing the hand.) )

2) Insert the circuit breaker handcart crank into the crank socket and press down hard, turn the crank counterclockwise, about 20 turns, remove the crank when the crank is obviously blocked and accompanied by a "click" sound, at this time the handcart is in the test position, the aviation plug lock is released, open the handcart room door, and manually disengage from the aviation plug. (The main circuit of the handcart is disconnected)

3) Push on the transfer trolley and lock it, pull out the circuit breaker trolley to the transfer trolley, and remove the transfer trolley. (When pulling the circuit breaker, you need to press the two push and pull handles of the circuit breaker to the middle, and at the same time pull back hard (pull outside the cabinet), after the circuit breaker is pulled to the transfer trolley and in place, let go of the push and pull handle, and the handle should be automatically reset.) )

4) Observe the live display and confirm that it is not charged before continuing the operation.

5) Insert the grounding switch operation handle into the hexagonal hole on the lower right side of the middle door, rotate clockwise to make the grounding switch in the closed position, confirm that the grounding switch has been closed, open the lower door of the cabinet, and maintenance personnel can enter maintenance and overhaul.

6) The grounding switch and the circuit breaker and the cabinet door are interlocked, only the circuit breaker is in the test position or withdrawn out of the cabinet can be combined and divided the grounding switch, and only after the grounding switch is opened, the circuit breaker can be shaken from the test position to the working position, and it cannot be forcibly operated. The grounding switch and the door under the cabinet can be urgently unlocked, and can only be urgently unlocked if it is confirmed that it is necessary, otherwise there is a risk of electric shock.

9. Electrical and mechanical interlocking related content

1) Main power supply and backup power supply

The main power supply (backup power supply) circuit breaker is equipped with electrical and mechanical interlock, the two circuit breakers can not be closed at the same time, when the main power circuit breaker is in the working position, the backup power supply can only be in the experimental position and cannot be closed. The reverse is true.

2) Main power supply (backup power supply) circuit breaker and metering handcart

Only the metering handcart in the working position is, the main power supply (backup power) circuit breaker can be closed, after the circuit breaker is closed, it is not allowed to shake out the metering handcart with load, when the pre-shake metering handcart is misoperated, the circuit breaker will immediately trip, and the signal screen alarm.

3) 1# outlet cabinet and 1# transformer (example)

1# outlet cabinet and 1 transformer with electrical interlock, when the transformer door is all closed, 1# outlet cabinet can be closed, if one of the doors is not closed, or all are not closed, then 1# outlet cabinet can not be closed.

4) 2 outlet cabinets and 2 transformers (example)

2 outlet cabinet and 1 transformer has an electrical interlock, when the transformer door is all closed, 2 outlet cabinet can be closed, if one of the doors is not closed, or all are not closed, then 2 outlet cabinet can not be closed.

5) Outlet cabinet circuit breaker and grounding switch

When the outlet cabinet is in the closed position, because of the mechanical interlock with the grounding switch, the grounding knife cannot be closed, and the grounding switch can be closed only when the circuit breaker is in the open state and in the test position.

Anhui Derun ElectricIt is a main production of 35kV and below high and low voltage switchgear, products exported to more than 30 countries around the world, reliable quality, thoughtful service. The commissioning engineers of Derun Electric have been trained by ABB, Schneider and other brand companies, and can wear ABB clothing to work. All are old engineers who have many years of on-site debugging experience, and have been unanimously praised by customers.